add ups apc input line mode

This commit is contained in:
Colin Gagnaire 2019-03-19 10:47:38 +01:00
parent b116fde99a
commit 2028d37dd3
2 changed files with 170 additions and 4 deletions

View File

@ -0,0 +1,165 @@
#
# Copyright 2019 Centreon (http://www.centreon.com/)
#
# Centreon is a full-fledged industry-strength solution that meets
# the needs in IT infrastructure and application monitoring for
# service performance.
#
# Licensed under the Apache License, Version 2.0 (the "License");
# you may not use this file except in compliance with the License.
# You may obtain a copy of the License at
#
# http://www.apache.org/licenses/LICENSE-2.0
#
# Unless required by applicable law or agreed to in writing, software
# distributed under the License is distributed on an "AS IS" BASIS,
# WITHOUT WARRANTIES OR CONDITIONS OF ANY KIND, either express or implied.
# See the License for the specific language governing permissions and
# limitations under the License.
#
package hardware::ups::apc::snmp::mode::inputlines;
use base qw(centreon::plugins::templates::counter);
use strict;
use warnings;
use centreon::plugins::templates::catalog_functions qw(catalog_status_threshold);
sub custom_status_output {
my ($self, %options) = @_;
my $msg = sprintf("Last input line fail cause is '%s'", $self->{result_values}->{last_cause});
return $msg;
}
sub custom_status_calc {
my ($self, %options) = @_;
$self->{result_values}->{last_cause} = $options{new_datas}->{$self->{instance} . '_upsAdvInputLineFailCause'};
return 0;
}
sub set_counters {
my ($self, %options) = @_;
$self->{maps_counters_type} = [
{ name => 'global', type => 0 },
];
$self->{maps_counters}->{global} = [
{ label => 'voltage', set => {
key_values => [ { name => 'upsAdvInputLineVoltage' } ],
output_template => 'Voltage : %s V',
perfdatas => [
{ label => 'voltage', value => 'upsAdvInputLineVoltage_absolute', template => '%s',
unit => 'V' },
],
}
},
{ label => 'frequence', set => {
key_values => [ { name => 'upsAdvInputFrequency' } ],
output_template => 'Frequence : %s Hz',
perfdatas => [
{ label => 'frequence', value => 'upsAdvInputFrequency_absolute', template => '%s',
unit => 'Hz' },
],
}
},
{ label => 'status', threshold => 0, set => {
key_values => [ { name => 'upsAdvInputLineFailCause' } ],
closure_custom_calc => $self->can('custom_status_calc'),
closure_custom_output => $self->can('custom_status_output'),
closure_custom_perfdata => sub { return 0; },
closure_custom_threshold_check => \&catalog_status_threshold,
}
},
];
}
sub new {
my ($class, %options) = @_;
my $self = $class->SUPER::new(package => __PACKAGE__, %options);
bless $self, $class;
$self->{version} = '1.0';
$options{options}->add_options(arguments => {
"warning-status:s" => { name => 'warning_status', default => '' },
"critical-status:s" => { name => 'critical_status', default => '' },
});
return $self;
}
sub check_options {
my ($self, %options) = @_;
$self->SUPER::check_options(%options);
$self->change_macros(macros => ['warning_status', 'critical_status']);
}
my %map_status = (
1 => 'noTransfer', 2 => 'highLineVoltage', 3 => 'brownout', 4 => 'blackout',
5 => 'smallMomentarySag', 6 => 'deepMomentarySag', 7 => 'smallMomentarySpike',
8 => 'largeMomentarySpike', 9 => 'selfTest', 10 => 'rateOfVoltageChange',
);
my $mapping = {
upsAdvInputLineVoltage => { oid => '.1.3.6.1.4.1.318.1.1.1.3.2.1' },
upsAdvInputFrequency => { oid => '.1.3.6.1.4.1.318.1.1.1.3.2.4' },
upsAdvInputLineFailCause => { oid => '.1.3.6.1.4.1.318.1.1.1.3.2.5', map => \%map_status },
};
my $oid_upsAdvInput = '.1.3.6.1.4.1.318.1.1.1.3.2';
sub manage_selection {
my ($self, %options) = @_;
$self->{global} = {};
my $snmp_result = $options{snmp}->get_table(oid => $oid_upsAdvInput,
nothing_quit => 1);
my $result = $options{snmp}->map_instance(mapping => $mapping, results => $snmp_result, instance => '0');
foreach my $name (keys %{$mapping}) {
$self->{global}->{$name} = $result->{$name};
}
}
1;
__END__
=head1 MODE
Check input lines.
=over 8
=item B<--filter-counters>
Only display some counters (regexp can be used).
Example: --filter-counters='^frequence|voltage$'
=item B<--warning-status>
Set warning threshold for status (Default: '').
Can used special variables like: %{last_cause}
=item B<--critical-status>
Set critical threshold for status (Default: '').
Can used special variables like: %{last_cause}
=item B<--warning-*>
Threshold warning.
Can be: 'voltage', 'frequence'.
=item B<--critical-*>
Threshold critical.
Can be: 'voltage', 'frequence'.
=back
=cut

View File

@ -30,6 +30,7 @@ sub new {
$self->{version} = '0.1';
%{$self->{modes}} = (
'battery-status' => 'hardware::ups::apc::snmp::mode::batterystatus',
'input-lines' => 'hardware::ups::apc::snmp::mode::inputlines',
'output-lines' => 'hardware::ups::apc::snmp::mode::outputlines',
'sensors' => 'hardware::ups::apc::snmp::mode::sensors',
);