diff --git a/hardware/devices/eltek/enexus/snmp/mode/battery.pm b/hardware/devices/eltek/enexus/snmp/mode/battery.pm index 29857b605..652603bde 100644 --- a/hardware/devices/eltek/enexus/snmp/mode/battery.pm +++ b/hardware/devices/eltek/enexus/snmp/mode/battery.pm @@ -139,14 +139,14 @@ sub set_counters { { value => 'current_absolute', template => '%.2f', min => 0, unit => 'A' } ] } - }, + } ]; } sub prefix_battery_output { my ($self, %options) = @_; - return "Battery "; + return 'Battery '; } sub new { @@ -228,9 +228,6 @@ sub threshold_eltek_configured { sub manage_selection { my ($self, %options) = @_; - # we can calculate the time remaining if unit is ah (amperehour). - - my $oid_outputControlUnitOutputEntry = '.1.3.6.1.4.1.12148.10.12.2.1'; my $snmp_result = $options{snmp}->get_leef( oids => [ map($_->{oid} . '.0', values(%$mapping)) ], nothing_quit => 1 @@ -248,6 +245,7 @@ sub manage_selection { charge_remaining => $result->{batteryRemainingCapacityValue}, charge_remaining_unit => $result->{powerSystemCapacityScale} }; + # we can calculate the time remaining if unit is ah (amperehour) and current battery is discharging (negative value) if ($result->{powerSystemCapacityScale} eq 'ah' && $result->{batteryCurrentsValue} < 0) { $self->{battery}->{charge_remaining_time} = int($result->{batteryRemainingCapacityValue} * 3600 / $result->{batteryCurrentsValue} * $scale_current * -1); diff --git a/hardware/devices/eltek/enexus/snmp/mode/load.pm b/hardware/devices/eltek/enexus/snmp/mode/load.pm new file mode 100644 index 000000000..5c80df04e --- /dev/null +++ b/hardware/devices/eltek/enexus/snmp/mode/load.pm @@ -0,0 +1,222 @@ +# +# Copyright 2020 Centreon (http://www.centreon.com/) +# +# Centreon is a full-fledged industry-strength solution that meets +# the needs in IT infrastructure and application monitoring for +# service performance. +# +# Licensed under the Apache License, Version 2.0 (the "License"); +# you may not use this file except in compliance with the License. +# You may obtain a copy of the License at +# +# http://www.apache.org/licenses/LICENSE-2.0 +# +# Unless required by applicable law or agreed to in writing, software +# distributed under the License is distributed on an "AS IS" BASIS, +# WITHOUT WARRANTIES OR CONDITIONS OF ANY KIND, either express or implied. +# See the License for the specific language governing permissions and +# limitations under the License. +# + +package hardware::devices::eltek::enexus::snmp::mode::load; + +use base qw(centreon::plugins::templates::counter); + +use strict; +use warnings; +use centreon::plugins::templates::catalog_functions qw(catalog_status_threshold catalog_status_calc); +use Digest::MD5 qw(md5_hex); + +sub custom_status_output { + my ($self, %options) = @_; + + return sprintf('status: %s', + $self->{result_values}->{status} + ); +} + +sub set_counters { + my ($self, %options) = @_; + + $self->{maps_counters_type} = [ + { name => 'load', type => 0, cb_prefix_output => 'prefix_load_output', skipped_code => { -10 => 1 } }, + { name => 'phase', type => 1, cb_prefix_output => 'prefix_phase_output', message_multiple => 'All phases are ok', skipped_code => { -10 => 1 } } + ]; + + $self->{maps_counters}->{load} = [ + { label => 'status', threshold => 0, set => { + key_values => [ { name => 'status' } ], + closure_custom_calc => \&catalog_status_calc, + closure_custom_output => $self->can('custom_status_output'), + closure_custom_perfdata => sub { return 0; }, + closure_custom_threshold_check => \&catalog_status_threshold + } + }, + { label => 'current', nlabel => 'load.current.ampere', set => { + key_values => [ { name => 'current' } ], + output_template => 'current: %s A', + perfdatas => [ + { value => 'current_absolute', template => '%s', unit => 'A', min => 0 } + ] + } + }, + { label => 'energy-delivered', nlabel => 'load.energy.delivered.watt', display_ok => 0, set => { + key_values => [ { name => 'energy', diff => 1 } ], + output_template => 'accumulated energy delivered: %s W', + perfdatas => [ + { value => 'energy_absolute', template => '%s', unit => 'W', min => 0 } + ] + } + } + ]; + + $self->{maps_counters}->{phase} = [ + { label => 'voltage', nlabel => 'phase.voltage.volt', set => { + key_values => [ { name => 'voltage' } ], + output_template => 'voltage: %.2f V', + perfdatas => [ + { value => 'voltage_absolute', template => '%.2f', unit => 'V', label_extra_instance => 1 } + ] + } + } + ]; +} + +sub prefix_load_output { + my ($self, %options) = @_; + + return 'Load '; +} + +sub prefix_phase_output { + my ($self, %options) = @_; + + return "Phase '" . $options{instance_value}->{display} . "' "; +} + +sub new { + my ($class, %options) = @_; + my $self = $class->SUPER::new(package => __PACKAGE__, %options, statefile => 1, force_new_perfdata => 1); + bless $self, $class; + + $options{options}->add_options(arguments => { + 'unknown-status:s' => { name => 'unknown_status', default => '' }, + 'warning-status:s' => { name => 'warning_status', default => '%{status} =~ /minor|warning/i' }, + 'critical-status:s' => { name => 'critical_status', default => '%{status} =~ /error|major|critical/i' } + }); + + return $self; +} + +sub check_options { + my ($self, %options) = @_; + $self->SUPER::check_options(%options); + + $self->change_macros(macros => [ + 'warning_status', 'critical_status', 'unknown_status', + ]); +} + +my $map_status = { + 0 => 'error', 1 => 'normal', 2 => 'minorAlarm', 3 => 'majorAlarm', + 4 => 'disabled', 5 => 'disconnected', 6 => 'notPresent', + 7 => 'minorAndMajor', 8 => 'majorLow', 9 => 'minorLow', + 10 => 'majorHigh', 11 => 'minorHigh', 12 => 'event', + 13 => 'valueVolt', 14 => 'valueAmp', 15 => 'valueTemp', + 16 => 'valueUnit', 17 => 'valuePerCent', 18 => 'critical', + 19 => 'warning' +}; +my $map_decimal_setting = { 0 => 'ampere', 1 => 'deciAmpere' }; + +my $mapping = { + powerSystemCurrentDecimalSetting => { oid => '.1.3.6.1.4.1.12148.10.2.15', map => $map_decimal_setting }, + loadStatus => { oid => '.1.3.6.1.4.1.12148.10.9.1', map => $map_status }, + loadCurrentValue => { oid => '.1.3.6.1.4.1.12148.10.9.2.5' }, # A or dA + loadCurrentMajorHighLevel => { oid => '.1.3.6.1.4.1.12148.10.9.2.6' }, + loadCurrentMinorHighLevel => { oid => '.1.3.6.1.4.1.12148.10.9.2.7' }, + loadEnergyLogAccumulated => { oid => '.1.3.6.1.4.1.12148.10.9.8.1' }, # Watt +}; + +sub threshold_eltek_configured { + my ($self, %options) = @_; + + if ((!defined($self->{option_results}->{'critical-' . $options{label}}) || $self->{option_results}->{'critical-' . $options{label}} eq '') && + (!defined($self->{option_results}->{'warning-' . $options{label}}) || $self->{option_results}->{'warning-' . $options{label}} eq '')) { + my ($crit, $warn) = ('', ''); + $crit = $options{low_crit} . ':' if (defined($options{low_crit}) && $options{low_crit} ne ''); + $crit .= $options{high_crit} if (defined($options{high_crit}) && $options{high_crit} ne ''); + $warn = $options{low_warn} . ':' if (defined($options{low_warn}) && $options{low_warn} ne ''); + $warn .= $options{high_warn} if (defined($options{high_warn}) && $options{high_warn} ne ''); + $self->{perfdata}->threshold_validate(label => 'critical-' . $options{label}, value => $crit); + $self->{perfdata}->threshold_validate(label => 'warning-' . $options{label}, value => $warn); + } +} + +sub manage_selection { + my ($self, %options) = @_; + + my $snmp_result = $options{snmp}->get_leef( + oids => [ map($_->{oid} . '.0', values(%$mapping)) ], + nothing_quit => 1 + ); + my $result = $options{snmp}->map_instance(mapping => $mapping, results => $snmp_result, instance => '0'); + + my $scale_current = 1; + $scale_current = 0.1 if ($result->{powerSystemCurrentDecimalSetting} eq 'deciAmpere'); + $self->{load} = { + status => $result->{loadStatus}, + energy => $result->{loadEnergyLogAccumulated}, + current => $result->{loadCurrentValue} * $scale_current + }; + + $self->threshold_eltek_configured( + label => 'load-current-ampere', + high_crit => $result->{loadCurrentMajorHighLevel} * $scale_current, + high_warn => $result->{loadCurrentMinorHighLevel} * $scale_current + ); + + my $oid_loadVoltageValue = '.1.3.6.1.4.1.12148.10.9.9.1.6'; + $snmp_result = $options{snmp}->get_table(oid => $oid_loadVoltageValue); + $self->{phase} = {}; + foreach (keys %$snmp_result) { + /\.(\d+)$/; + $self->{phase}->{$1} = { display => $1, voltage => $snmp_result->{$_} * 0.01 }; + } + + $self->{cache_name} = 'eltek_enexus_' . $self->{mode} . '_' . $options{snmp}->get_hostname() . '_' . $options{snmp}->get_port() . '_' . + (defined($self->{option_results}->{filter_counters}) ? md5_hex($self->{option_results}->{filter_counters}) : md5_hex('all')); +} + +1; + +__END__ + +=head1 MODE + +Check load. + +=over 8 + +=item B<--unknown-status> + +Set unknown threshold for status. +Can used special variables like: %{status} + +=item B<--warning-status> + +Set warning threshold for status (Default: '%{status} =~ /minor|warning/i'). +Can used special variables like: %{status} + +=item B<--critical-status> + +Set critical threshold for status (Default: '%{status} =~ /error|major|critical/i'). +Can used special variables like: %{status} + +=item B<--warning-*> B<--critical-*> + +Thresholds. +Can be: 'current', 'energy-delivered'. + +=back + +=cut diff --git a/hardware/devices/eltek/enexus/snmp/plugin.pm b/hardware/devices/eltek/enexus/snmp/plugin.pm index 297ae1605..b6fd4245c 100644 --- a/hardware/devices/eltek/enexus/snmp/plugin.pm +++ b/hardware/devices/eltek/enexus/snmp/plugin.pm @@ -33,6 +33,7 @@ sub new { %{$self->{modes}} = ( 'alarms' => 'hardware::devices::eltek::enexus::snmp::mode::alarms', 'battery' => 'hardware::devices::eltek::enexus::snmp::mode::battery', + 'load' => 'hardware::devices::eltek::enexus::snmp::mode::load', 'outputs' => 'hardware::devices::eltek::enexus::snmp::mode::outputs' );