*** Settings ***
Documentation Check UPS APC Sensors
Resource ${CURDIR}${/}..${/}..${/}..${/}..${/}resources/import.resource
Suite Setup Ctn Generic Suite Setup
Test Timeout 120s
*** Variables ***
${CMD} ${CENTREON_PLUGINS}
... --plugin=hardware::ups::apc::snmp::plugin
... --hostname=${HOSTNAME}
... --mode=sensors
... --snmp-version=${SNMPVERSION}
... --snmp-port=${SNMPPORT}
... --snmp-timeout=1
*** Test Cases ***
apc galaxy ${tc}
[Tags] hardware ups apc
${command} Catenate
... ${CMD}
... --snmp-community=hardware/ups/apc/snmp/ups-apc-galaxy
... ${extra_options}
Ctn Run Command And Check Result As Strings ${command} ${expected_result}
Examples: tc extra_options expected_result --
... 1 ${EMPTY} OK: All 1 components are ok [1/1 sensors]. | 'ambient#sensor.ambient.temperature.celsius'=21C;;;; 'hardware.sensor.count'=1;;;;
... 2 --critical=temperature,.*,:10 CRITICAL: temperature 'ambient' is 21 C | 'ambient#sensor.ambient.temperature.celsius'=21C;;0:10;; 'hardware.sensor.count'=1;;;;
... 3 --filter=sensor --no-component=WARNING WARNING: No components are checked.
*** Test Cases ***
apc others ${tc}
[Tags] hardware ups apc
${command} Catenate
... ${CMD}
... --snmp-community=hardware/ups/apc/snmp/ups-apc-sensors
... ${extra_options}
Ctn Run Command And Check Result As Strings ${command} ${expected_result}
Examples: tc extra_options expected_result --
... 1 ${EMPTY} CRITICAL: integrated sensor 'YYYYY Rack 1' status is 'disconnected' WARNING: universal sensor 'Humi XXX' status is 'uioWarning' | 'Temp XXX#sensor.universal.temperature.celsius'=24C;;;; 'Temp XXX#sensor.universal.humidity.percentage'=45%;;;0;100 'Humi XXX#sensor.universal.temperature.celsius'=25C;;;; 'Humi XXX#sensor.universal.humidity.percentage'=44%;;;0;100 'YYYYY Rack 2#sensor.integrated.temperature.celsius'=29C;;;; 'YYYYY Rack 2#sensor.integrated.humidity.percentage'=52%;;;0;100 'hardware.sensor.count'=4;;;;
... 2 --threshold-overload='sensor,WARNING,disconnected' WARNING: universal sensor 'Humi XXX' status is 'uioWarning' - integrated sensor 'YYYYY Rack 1' status is 'disconnected' | 'Temp XXX#sensor.universal.temperature.celsius'=24C;;;; 'Temp XXX#sensor.universal.humidity.percentage'=45%;;;0;100 'Humi XXX#sensor.universal.temperature.celsius'=25C;;;; 'Humi XXX#sensor.universal.humidity.percentage'=44%;;;0;100 'YYYYY Rack 2#sensor.integrated.temperature.celsius'=29C;;;; 'YYYYY Rack 2#sensor.integrated.humidity.percentage'=52%;;;0;100 'hardware.sensor.count'=4;;;;
... 3 --filter=sensor,1 WARNING: universal sensor 'Humi XXX' status is 'uioWarning' | 'Humi XXX#sensor.universal.temperature.celsius'=25C;;;; 'Humi XXX#sensor.universal.humidity.percentage'=44%;;;0;100 'YYYYY Rack 2#sensor.integrated.temperature.celsius'=29C;;;; 'YYYYY Rack 2#sensor.integrated.humidity.percentage'=52%;;;0;100 'hardware.sensor.count'=2;;;;
... 4 --filter=sensor,1 --critical='temperature,.*,20' CRITICAL: universal sensor temperature 'Humi XXX' is 25 C - integrated sensor temperature 'YYYYY Rack 2' is 29 celsius WARNING: universal sensor 'Humi XXX' status is 'uioWarning' | 'Humi XXX#sensor.universal.temperature.celsius'=25C;;0:20;; 'Humi XXX#sensor.universal.humidity.percentage'=44%;;;0;100 'YYYYY Rack 2#sensor.integrated.temperature.celsius'=29C;;0:20;; 'YYYYY Rack 2#sensor.integrated.humidity.percentage'=52%;;;0;100 'hardware.sensor.count'=2;;;;