centreon-plugins/hardware/ups/standard/rfc1628/mode/batterystatus.pm

157 lines
6.7 KiB
Perl

################################################################################
# Copyright 2005-2013 MERETHIS
# Centreon is developped by : Julien Mathis and Romain Le Merlus under
# GPL Licence 2.0.
#
# This program is free software; you can redistribute it and/or modify it under
# the terms of the GNU General Public License as published by the Free Software
# Foundation ; either version 2 of the License.
#
# This program is distributed in the hope that it will be useful, but WITHOUT ANY
# WARRANTY; without even the implied warranty of MERCHANTABILITY or FITNESS FOR A
# PARTICULAR PURPOSE. See the GNU General Public License for more details.
#
# You should have received a copy of the GNU General Public License along with
# this program; if not, see <http://www.gnu.org/licenses>.
#
# Linking this program statically or dynamically with other modules is making a
# combined work based on this program. Thus, the terms and conditions of the GNU
# General Public License cover the whole combination.
#
# As a special exception, the copyright holders of this program give MERETHIS
# permission to link this program with independent modules to produce an executable,
# regardless of the license terms of these independent modules, and to copy and
# distribute the resulting executable under terms of MERETHIS choice, provided that
# MERETHIS also meet, for each linked independent module, the terms and conditions
# of the license of that module. An independent module is a module which is not
# derived from this program. If you modify this program, you may extend this
# exception to your version of the program, but you are not obliged to do so. If you
# do not wish to do so, delete this exception statement from your version.
#
# For more information : contact@centreon.com
# Authors : Quentin Garnier <qgarnier@merethis.com>
#
####################################################################################
package hardware::ups::standard::rfc1628::mode::batterystatus;
use base qw(centreon::plugins::mode);
use strict;
use warnings;
my %battery_status = (
1 => ['unknown', 'UNKNOWN'],
2 => ['normal', 'OK'],
3 => ['low', 'WARNING'],
4 => ['depleted', 'CRITICAL'],
);
sub new {
my ($class, %options) = @_;
my $self = $class->SUPER::new(package => __PACKAGE__, %options);
bless $self, $class;
$self->{version} = '1.0';
$options{options}->add_options(arguments =>
{
"warning:s" => { name => 'warning', },
"critical:s" => { name => 'critical', },
});
return $self;
}
sub check_options {
my ($self, %options) = @_;
$self->SUPER::init(%options);
if (($self->{perfdata}->threshold_validate(label => 'warning', value => $self->{option_results}->{warning})) == 0) {
$self->{output}->add_option_msg(short_msg => "Wrong warning threshold '" . $self->{option_results}->{warning} . "'.");
$self->{output}->option_exit();
}
if (($self->{perfdata}->threshold_validate(label => 'critical', value => $self->{option_results}->{critical})) == 0) {
$self->{output}->add_option_msg(short_msg => "Wrong critical threshold '" . $self->{option_results}->{critical} . "'.");
$self->{output}->option_exit();
}
}
sub run {
my ($self, %options) = @_;
# $options{snmp} = snmp object
$self->{snmp} = $options{snmp};
my $oid_upsBattery = '.1.3.6.1.2.1.33.1.2';
my $oid_upsBatteryStatus = '.1.3.6.1.2.1.33.1.2.1.0';
my $oid_upsEstimatedMinutesRemaining = '.1.3.6.1.2.1.33.1.2.3.0';
my $oid_upsEstimatedChargeRemaining = '.1.3.6.1.2.1.33.1.2.4.0';
my $oid_upsBatteryVoltage = '.1.3.6.1.2.1.33.1.2.5.0'; # in dV
my $oid_upsBatteryCurrent = '.1.3.6.1.2.1.33.1.2.6.0'; # in dA
my $oid_upsBatteryTemperature = '.1.3.6.1.2.1.33.1.2.7.0'; # in degrees Centigrade
my $result = $self->{snmp}->get_table(oid => $oid_upsBattery, nothing_quit => 1);
my $current = defined($result->{$oid_upsBatteryCurrent}) ? $result->{$oid_upsBatteryCurrent} * 0.1 : 0;
my $voltage = defined($result->{$oid_upsBatteryVoltage}) ? $result->{$oid_upsBatteryVoltage} * 0.1 : 0;
my $temp = defined($result->{$oid_upsBatteryTemperature}) ? $result->{$oid_upsBatteryTemperature} : 0;
my $min_remain = defined($result->{$oid_upsEstimatedMinutesRemaining}) ? $result->{$oid_upsEstimatedMinutesRemaining} : 'unknown';
my $charge_remain = defined($result->{$oid_upsEstimatedChargeRemaining}) ? $result->{$oid_upsEstimatedChargeRemaining} : 'unknown';
my $status = defined($result->{$oid_upsBatteryStatus}) ? $result->{$oid_upsBatteryStatus} : 1; # we put unknown ???
$self->{output}->output_add(severity => ${$battery_status{$status}}[1],
short_msg => sprintf("Battery status is %s", ${$battery_status{$status}}[0]));
my $exit_code = 'ok';
if ($charge_remain ne 'unknown') {
$exit_code = $self->{perfdata}->threshold_check(value => $charge_remain,
threshold => [ { label => 'critical', 'exit_litteral' => 'critical' }, { label => 'warning', exit_litteral => 'warning' } ]);
$self->{output}->perfdata_add(label => 'load', unit => '%',
value => $charge_remain,
warning => $self->{perfdata}->get_perfdata_for_output(label => 'warning'),
critical => $self->{perfdata}->get_perfdata_for_output(label => 'critical'),
min => 0, max => 100);
}
$self->{output}->output_add(severity => $exit_code,
short_msg => sprintf("Charge remaining: %s%% (%s minutes remaining)", $charge_remain, $min_remain));
if ($current != 0) {
$self->{output}->perfdata_add(label => 'current', unit => 'A',
value => $current,
);
}
if ($voltage != 0) {
$self->{output}->perfdata_add(label => 'voltage', unit => 'V',
value => $voltage,
);
}
if ($temp != 0) {
$self->{output}->perfdata_add(label => 'temp', unit => 'C',
value => $temp,
);
}
$self->{output}->display();
$self->{output}->exit();
}
1;
__END__
=head1 MODE
Check Battery Status and battery charge remaining.
=over 8
=item B<--warning>
Threshold warning in percent of charge remaining.
=item B<--critical>
Threshold critical in percent of charge remaining.
=back
=cut